Data hall pod A

DC1 - Data hall 1, row A · rev 1.0 · design

2 rack(s)11 device(s)16 cable(s) 0 error(s)0 warning(s)
switchrouterfirewallserverstoragepatch-paneloutletcable-managerblankingshelfupskvmotherpdu

Planning aid generated from the model. Verify dimensions, weights and power against datasheets and the site before installation. Hover a unit for details.

A01 compute

ROW-A · 42U · 19" · 1200 mm deep · 4-post · front 8/42U used · 125.0/1000 kg · 5000 W (max) · 17060 BTU/h · front faces cold aisle

FRONT123456789101112131415161718192021222324252627282930313233343536373839404142A01-PDU-A (a01-pdu-a) · 0U left · feed AAA01-PDU-B (a01-pdu-b) · 0U right · feed BBA01-LEAF-1 (leaf1) Generic Leaf 48x25G + 6x100G, port-side exhaust U42 · switch · rear of equipment role: leafA01-LEAF-1 (rear)A01-LEAF-2 (leaf2) Generic Leaf 48x25G + 6x100G, port-side exhaust U41 · switch · rear of equipment role: leafA01-LEAF-2 (rear)SRV-01 (srv01) Generic 1U rack server, 2x25G + 2x1G + BMC U23 · serverSRV-01SRV-02 (srv02) Generic 1U rack server, 2x25G + 2x1G + BMC U22 · serverSRV-02SRV-03 (srv03) Generic 1U rack server, 2x25G + 2x1G + BMC U21 · serverSRV-03SRV-04 (srv04) Generic 1U rack server, 2x25G + 2x1G + BMC U20 · serverSRV-04STOR-01 (st1) Generic 2U storage array, 4x25G + mgmt U10-U11 · storageSTOR-01REAR123456789101112131415161718192021222324252627282930313233343536373839404142A01-PDU-A (a01-pdu-a) · 0U left · feed AAA01-PDU-B (a01-pdu-b) · 0U right · feed BBA01-LEAF-1 (leaf1) Generic Leaf 48x25G + 6x100G, port-side exhaust U42 · switch role: leafA01-LEAF-1A01-LEAF-2 (leaf2) Generic Leaf 48x25G + 6x100G, port-side exhaust U41 · switch role: leafA01-LEAF-2A01-FP (fp1) Generic 24-port LC duplex fiber panel 1U U40 · patch-panelA01-FPA01-CM (cm1) Generic Horizontal cable manager 1U U39 · cable-managerA01-CMSRV-01 (srv01) Generic 1U rack server, 2x25G + 2x1G + BMC U23 · server · rear of equipmentSRV-01 (rear)SRV-02 (srv02) Generic 1U rack server, 2x25G + 2x1G + BMC U22 · server · rear of equipmentSRV-02 (rear)SRV-03 (srv03) Generic 1U rack server, 2x25G + 2x1G + BMC U21 · server · rear of equipmentSRV-03 (rear)SRV-04 (srv04) Generic 1U rack server, 2x25G + 2x1G + BMC U20 · server · rear of equipmentSRV-04 (rear)STOR-01 (st1) Generic 2U storage array, 4x25G + mgmt U10-U11 · storage · rear of equipmentSTOR-01 (rear)

A02 network

ROW-A · 42U · 19" · 1200 mm deep · 4-post · front 2/42U used · 12.0/1000 kg · 700 W (max) · 2388 BTU/h · front faces cold aisle

FRONT123456789101112131415161718192021222324252627282930313233343536373839404142A02-PDU-A (a02-pdu-a) · 0U left · feed AAA02-PDU-B (a02-pdu-b) · 0U right · feed BBA02-FP (fp2) Generic 24-port LC duplex fiber panel 1U U42 · patch-panelA02-FPA02-SPINE-1 (spine1) Generic Spine switch 32x100G QSFP28 U40 · switch role: spineA02-SPINE-1REAR123456789101112131415161718192021222324252627282930313233343536373839404142A02-PDU-A (a02-pdu-a) · 0U left · feed AAA02-PDU-B (a02-pdu-b) · 0U right · feed BBA02-SPINE-1 (spine1) Generic Spine switch 32x100G QSFP28 U40 · switch · rear of equipment role: spineA02-SPINE-1 (rear)

Findings

SeverityCodeFinding
infoRCD-AIR-BLANKINGRack "A01" has 34 open unit(s) on the cold face (U1-U9, U12-U19, U24-U40); fit blanking panels to stop hot-air recirculation.
infoRCD-AIR-BLANKINGRack "A02" has 40 open unit(s) on the cold face (U1-U39, U41); fit blanking panels to stop hot-air recirculation.